Vertiv Liebert GXT5 1ph UPS, 10kVA, input plug - hardwired, 5U, output – 230V, hardwired, output socket groups (4)C13 & (4)C19Technical characteristics of 10 kVA
GXT5-10KIRT5UXLE
Power (VA/W) 10,000 VA/10,000 W
Dimensions, inches (mm)
Unit (W x D x H) 16,9×24,8×8,5(430×630×217)
Weight, pounds (kg)
Ag-t 298 (135.2)
Input AC current parameters
Rated operating frequency
50 or 60 Hz
(Factory default value: 50)
Voltage range 230 V AC
Input cable
With cable connection
(shared or split bypass)
Output AC current parameters
Output connectors
With cable connection
4(C19), 4 (C13)
Default AC frequency
230 V AC
50 Hz or 60 Hz, Nominal value
Curve shape (battery life) Sinusoidal
Overload in the power supply network
>150 %, min. 200 ms; 125-150 %
for 60 seconds; 105-125 % for
5 minutes; ≤105 % continuously
Battery
Type Sealed, lead-acid,
with valve control
Battery life (100% load) 2 min
Battery life (50% load) 7 min
+ 1 external battery cabinet (100% load) 7 min
+ 1 external battery cabinet (50% load) 19 min
Requirements for environmental conditions
Operating temperature,°F (°C)
+32 to + 104 (0 to 40)
(without power reduction)
Storage temperature, °F (°C) From +5 to 122 (from -15 to 50)
Relative humidity
From 0 % to 95 %
(non-condensing)
Working height above sea level
Up to 3000 m (10,000 ft) at 25 ° C
(77 °F) without deterioration of rated
performance
Acoustic noise
< 55 dBA, 1 meter from the back
of the device
< 50 dBA, 1 meter to the side of
the device and in front of it
Regulatory compliance
Resistance to voltage surges
IEC/EN EN61000-4-5, Level 3,
criterion A
ISTA transportation, procedure 1E
Security Version IEC62040-1:2008, GS mark
Radiation IEC/EN/AS 62040-2 2nd ed. (Cat 2)
Standard 2 years; extension 1 and 3 years